SmartFan®Nimbus Manual

Fixed Speed Control Mode

SETTING CONTROL MODES (switches #7, 8)

Unless otherwise specified, the Nimbus is factory set to control fans in the Temperature Control mode. To control via a current or voltage source, remote powered transducer or fixed speed setting, set switches 7 and 8 as shown below, then refer to the control mode section you have selected to customize the Nimbus for your application.

Table 2: Setting Control Modes
Control Via Dip switch
7 8
Current or Voltage ON OFF
Remote Powered Transducer OFF ON
Temperature OFF OFF
Fixed Speed ON ON

USING FIXED SPEED MODE

Automatic speed control can be overridden in the fixed speed mode. To set the Nimbus to fixed speed mode, see table 2. In the fixed speed mode, the user can select motor voltages from 27% to 99% (in 1% or 2% increments) of supply voltage using DIP switches 1 through 6, see table 7.

Table 7: Fixed Speed Settings
% voltage DIP switch settings
1 2 3 4 5 6
27% OFF OFF OFF OFF OFF OFF
28% ON OFF OFF OFF OFF OFF
30% OFF ON OFF OFF OFF OFF
32% ON ON OFF OFF OFF OFF
33% OFF OFF ON OFF OFF OFF
35% ON OFF ON OFF OFF OFF
36% OFF ON ON OFF OFF OFF
37% ON ON ON OFF OFF OFF
39% OFF OFF OFF ON OFF OFF
40% ON OFF OFF ON OFF OFF
41% OFF ON OFF ON OFF OFF
42% ON ON OFF ON OFF OFF
43% OFF OFF ON ON OFF OFF
44% ON OFF ON ON OFF OFF
45% OFF ON ON ON OFF OFF
47% ON ON ON ON OFF OFF
48% OFF OFF OFF OFF ON OFF
49% ON OFF OFF OFF ON OFF
50% OFF ON OFF OFF ON OFF
51% ON ON OFF OFF ON OFF
53% OFF OFF ON OFF ON OFF
54% ON OFF ON OFF ON OFF
55% OFF ON ON OFF ON OFF
56% ON ON ON OFF ON OFF
57% OFF OFF OFF ON ON OFF
58% ON OFF OFF ON ON OFF
60% OFF ON OFF ON ON OFF
61% ON ON OFF ON ON OFF
62% OFF OFF ON ON ON OFF
63% ON OFF ON ON ON OFF
64% OFF ON ON ON ON OFF
65% ON ON ON ON ON OFF
67% OFF OFF OFF OFF OFF ON
68% ON OFF OFF OFF OFF ON
69% OFF ON OFF OFF OFF ON
70% ON ON OFF OFF OFF ON
71% OFF OFF ON OFF OFF ON
72% ON OFF ON OFF OFF ON
74% OFF ON ON OFF OFF ON
75% ON ON ON OFF OFF ON
76% OFF OFF OFF ON OFF ON
77% ON OFF OFF ON OFF ON
78% OFF ON OFF ON OFF ON
79% ON ON OFF ON OFF ON
80% OFF OFF ON ON OFF ON
81% ON OFF ON ON OFF ON
82% OFF ON ON ON OFF ON
83% ON ON ON ON OFF ON
84% OFF OFF OFF OFF ON ON
85% ON OFF OFF OFF ON ON
86% OFF ON OFF OFF ON ON
87% ON ON OFF OFF ON ON
88% OFF OFF ON OFF ON ON
89% ON OFF ON OFF ON ON
90% OFF ON ON OFF ON ON
91% ON ON ON OFF ON ON
92% OFF OFF OFF ON ON ON
93% ON OFF OFF ON ON ON
94% OFF ON OFF ON ON ON
95% ON ON OFF ON ON ON
96% OFF OFF ON ON ON ON
97% ON OFF ON ON ON ON
98% OFF ON ON ON ON ON
99% ON ON ON ON ON ON

ADDITIONAL MANUAL PAGESOperation/Installation Manual

Use the links below for addtional manual pages or for a complete manual (9 pages), click on the Operation/Installation Manual PDF link above.

Back to top
Control Resources
For Engineers, by Engineers.
Since 1984.
Control Resources Inc., 11 Beaver Brook Road, Littleton, MA 01460 USA Tel: 978-486-4160 Fax: 978-486-4772 Email: sales@controlres.com