SmartFan®Nimbus Manual

Current or Voltage Control Mode

SETTING CONTROL MODES (switches #7, 8)

Unless otherwise specified, the Nimbus is factory set to control fans in the Temperature Control mode. To control via a current or voltage source, remote powered transducer or fixed speed setting, set switches 7 and 8 as shown below, then refer to the control mode section you have selected to customize the Nimbus for your application.

Table 2: Setting Control Modes
Control Via Dip switch
7 8
Current or Voltage ON OFF
Remote Powered Transducer OFF ON
Temperature OFF OFF
Fixed Speed ON ON

USING CURRENT OR VOLTAGE CONTROL MODE

Unless otherwise specified, the Nimbus is factory set to control fans in the “Temperature Control” mode. To switch to controlling fan speed via a “Control Signal”, refer to table 2. Select the type of control signal you are using [I for 0-20mA (30mA Max.) or V for 0-10VDC (12VDC max.)] using the jumper on header J1. The Nimbus can also be customized to accept other control schemes, contact customer service for details.
Setting Idle Speed (switch #2,3)

The idle speed is the minimum voltage (as a % of supply voltage) supplied to the fan. The Nimbus is factory set for idle speeds of 30, 40, 50 and 60% by setting DIP switches 2 and 3. The default idle setting is 50%. Other idle speeds can be supplied, contact customer service for details.

Table 3: Idle Speed DIP Switch Settings
% of Supply Voltage Dip switch
2 3
30% ON OFF
40% OFF ON
50% OFF OFF
60% ON ON

Fan On / Fan Off Feature (switch #1)

To turn fan(s) off below the set idle speed (see table 3), set switch #1 to the ON position. To keep fans running at idle speed below the set idle speed, set switch #1 to the OFF position.
Control Signal Loss Options (switch #6)
If the control signal is lost, (less than 4mA in I mode, less than 2VDC in V mode) when switch 6 is OFF fans will continue to idle or remain off. To send fans to full speed if the control signal is lost (less than 4mA in I mode, less than 2VDC in V mode) set switch 6 to the ON position.

SmartFan Nimbus RMS Fan Voltage vs. Control Signal
Figure 6